| RL/2 |
Model |
28 |
38 |
50 |
| Capacity (GPH)(1) |
2.6 - 9.0 |
3.2 - 12.2 |
4.0 - 16.0 |
| Combustion Air Motor |
Voltage (2)(3) |
120/1/60 |
120/1/60 or 230 - 460 - 575/3/60 |
230 - 460 - 575/3/60 |
| HP |
1/2 |
1/2 or 3/4 |
3/4 |
| Amperage Draw |
5.2 |
5.2 / 3.2 / 1.6 / 1.3 |
3.2 / 1.6 / 1.3 |
| Sound Levels |
dBA |
68.0 |
70.0 |
75.0 |
Max. Chamber Pressure ("w.c.) @ high fire |
1.5 |
1.6 |
1.2 |
(1) Ratings based on
140,000 Btu/Gallon for No.2 fuel oil. (2) Other
voltages available on request. (3) A separate 120/1/60
control voltage supply is required. |

| RL/M |
Model |
28 |
38 |
50 |
| Capacity (GPH)(1) |
2.4 - 9.0 |
2.7 - 12.2 |
3.5 - 16.0 |
| Combustion Air Motor |
Voltage (2)(3) |
120/1/60 |
230 - 460 - 575/3/60 |
230 - 460 - 575/3/60 |
| HP |
1/2 |
3/4 |
3/4 |
| Amperage Draw |
5.2 |
3.2 / 1.6 / 1.3 |
3.2 / 1.6 / 1.3 |
| Sound Levels |
dBA |
68.0 |
70.0 |
75.0 |
Max. Chamber Pressure ("w.c.) @ high fire |
1.5 |
1.6 |
1.8 |
(1) Ratings based on
140,000 Btu/Gallon for No.2 fuel oil. (2) Other
voltages available on request. (3) A separate 120/1/60
control voltage supply is required. |
|