| RS/M |
Model |
28 |
38 |
50 |
| Capacity (MBTUH)(1) |
198 - 1,232 |
266 - 1,665 |
321 - 2,201 |
Combustion Air Motor |
Voltage(2)(3) |
120/1/60 |
120/1/60 or 230-460-575/3/60 |
230-460-575/3/60 |
| HP |
1/2 |
1/2 or 3/4 |
3/4 |
| Amperage
Draw |
5.2 |
5.2 / 3.2 / 1.6 / 1.3 |
3.2 / 1.6 / 1.3 |
| Sound Levels |
dBA |
68.0 |
70.0 |
72.0 |
| Max. Chamber Pressure ("w.c.) @ high fire |
1.2 |
1.4 |
1.0 |
| Min. Gas Pressure ("w.c.)(4)(5) |
6.0 |
7.0 |
6.0 |
(1) Ratings based on 1,000 Btu/ft.3
and .64 specific gravity.
(2) Other
voltages available on request.
(3) A seperate 120/1/60 control voltage supply is required.
(4) Based on
natural gas. (5) Honeywell, Dungs and Siemens gas
trains available. |

| RS/1 |
Model |
28 |
38 |
| Capacity (MBTUH)(1) |
617 - 1,320 |
880 - 1,761 |
Combustion Air Motor |
Voltage(2)(3) |
120/1/60 |
120/1/60 |
| HP |
1/2 |
1/2 |
| Amperage
Draw |
5.2 |
5.2 |
| Sound Levels |
dBA |
70.0 |
72.0 |
| Max. Chamber Pressure ("w.c.) @ high fire |
0.6 |
0.7 |
| Min. Gas Pressure ("w.c.)(4)(5) |
6.0 |
7.0 |
(1) Raitings based on 1,000
Btu/ft.3 and .64 specific gravity.
(2) Other
voltages available on request.
(3) A seperate 120/1/60 control voltage supply is required.
(4) Based on
natural gas. (5) Honeywell, Dungs and Siemens gas
trains available. |
|